Adjustable Water Filling Valve with Vertical Design - AF0522A
Place of Origin: Shanghai China (Mainland) | Brand Name: ACOL | Model Number: AF0522A | Type: Floor Heating Parts |
Floor Heating Part Type: Automatic Water Filling Valve | Max. pressure inlet : 10bar: Pressure adjustment ranges: 0.3~4bar |
Overview:
Adjustable Water Filling Valve with Vertical Designis a device consisting of pressure reducing valve, stainless steel filter, shut-off valve and a check valve.
The adjustable water filling valve with vertical design with visual design, installed on the water inlet piping in sealed heating systems, and its main function is to maintain the pressure of the system stable at a set value, automatically filling up with water as required.
The adjustable water filling valve with vertical design has the characteristic of being pre-adjusting, which means that it can be adjusted at the required pressure value before the system charging phase.
After installation, during the filling or topping-off phase, the water feed will stop when the set pressure is reached.
Built-in shut-off valve and check valve
Large diaphragm-seat seal working surface, bigger 40% more than general product, guarantees greater precision and sensitivity to maintain its operating characteristics unchanged overtime.
Technical parameters:
Max. pressure inlet: | 10bar |
Pressure adjustment ranges: | 0.3~4bar |
Pre-pressure: | 1.5bar |
Max. temperature: | 80°C |
Connection: | G 3/4" male thread inlet and can match with other slipknot for G 1/2" male thread, G 1/2" female thread outlet |
Pressure meter connection: | G 1/4" |
Body material: | H59 brass |
Seal material: | NBR rubber |
Mounting instruction:
- Adjustable water filling valve with vertical design can be installed in either horizontal or vertical position. It is, however, vital that the unit is not installed upside down. Direction arrow is inlet.
- AF0520 automatic water filling valve, 0.2 bar pressure will be added by screwing the knob on the top one circle in clockwise direction, conversely, the pressure reduced.
AF0522 adjustable water filling valve, no need to install pressure meter, just adjust the pressure at a set value before filling.
- Adjustable Water Filling Valve, the outlet pressure should over 0.3bar than the static pressure, and the setting pressure should less than the filling pressure or it can not work normally. It is normally installed at water backflow part.
- Automatically filling, until it reaches the required valve.
- When filling water, the shut-off valve can be closed by hand.
- The valve disk can be cleaned or changed.
Packaging Detail:Carton Boxes |
Delivery Detail:1 day |